Calculator #012LV short circuit100 V to 1 000 VIEC 60909-0

Short-Circuit Current Calculator — LV, up to 1 kV (IEC 60909-0)

Scope: a.c. three-phase systems with a nominal voltage from 100 V to 1 000 V (IEC 60909-0:2016, Clause 1). The voltage factor comes from Table 1, the transformer correction from Formula (12a), the peak current from 8.1.2 including the 1,15 factor and the 1,8 cap for low-voltage networks, and the thermal equivalent current from Clause 14. One table holds the whole network — feeders, transformers, cables, busways, reactors, motor groups, generators and converter-fed units connecting named busbars — and the nodal admittance matrix is built and inverted at the busbar you mark as the fault. The built-in validation reproduces the worked 400 V example of IEC TR 60909-4:2000, clause 3, at all three fault locations.

Above 1 kV? Use the companion tool #002 Short-Circuit — MV 1 to 33 kV, which carries the medium-voltage element library, several parallel sources per busbar and the earthing-arrangement selector.
System and voltage factor
Minimum currents only - Formula (32), α = 0,004/K.
Upstream network
Project overview - every circuit, every busbar
Network

#ElementName From the libraryPRO From busbarTo busbar p1p2p3 p4p5p6p7
Result at the fault
Protective device at the fault point

Manufacturer data - it is not a tabulated value.
Leave 0 for a device without an I_cw rating (most MCBs and MCCBs).
From the device's tripping curve - the current that operates it within the time IEC 60364-4-41 Table 41.1 requires. 0 skips the check.
Fault level at every busbar, and the report

The same network, solved at each of its busbars in turn: the maximum regime, the minimum regime a protective device has to see, and the peak current at that point.

Glossary
Built-in validation tests
#CasePublishedComputedStatus

Every case is a value printed in IEC TR 60909-4:2000, clause 3 (the 400 V system of Figure 6) or in IEC 60909-0:2016 Table 1. The panel runs in your browser, so nothing here is taken on trust. How every other engine on the site is checked: calculation validation; how they are built: methodology.