Minimum cross-section of a protective conductor from the prospective fault current and the
disconnection time, by the adiabatic equation of IEC 60364-5-54:2011, 543.1.2. Valid only for
disconnection times up to 5 s; longer times require the non-adiabatic method of IEC 60949.